The procedure of transformer oil breakdown voltage test is given below:
To assess the insulating property of transformer oil, a sample of the transformer oil is taken and its breakdown voltage is measured.
• The transformer oil is filled in the vessel of the testing device. Two standard-compliant test electrodes with a typical clearance of 2.5mm are surrounded by the transformer oil;
• A test voltage is applied to the electrodes and is continuously increased up to the breakdown voltage with a constant, standard-compliant voltage boosting rate of 2kV/s;
• At a certain voltage level, breakdown occurs in an electric arc, leading to a collapse of the test voltage;
• An instant after ignitioin of the arc, the test voltage is switched off automatically by the testing device. Ultra fast switch off is high desirable, as the carbonisation due to the electric arc must be limited to keep the additional pollution as low as possible;
• The transformer oil testing device measures and reports the root mean square value of the breakdown voltage;
• After the transformer oil test is completed, the insulation oil is stirred automatically and the test sequence is performed repeatedly. Typically 5 repetitions (Test 5 times), depending on the standard;
• As a result, the breakdown voltage is calculated as mean value of the individual measurements;
• The lower the resulting breakdown voltage, the poorer the quality of the transformer oil.